USER MANUALEnglish 6 & 10 kVA 208V & 240V UPStation GXT™
10GXT6000T / 10000T - 208 UPS ONLY Models whose part number ends with a “208” are NOT fitted with an isolating output transformer and are NOT separ
11NOTES FOR GXT6000T / 10000T - 208 UPS ONLY 1. The installer must provide circuit breaker protection according to local codes. The UTILITY disconne
12GXT6000T / 10000T - 208X UPS ONLY Models whose part number ends with a “208X” are fitted with a single-phase isolating output transformer and are
13NOTES FOR GXT6000T / 10000T - 208X UPS ONLY 1. The installer must provide circuit breaker protection according to local codes. The utility disconn
14GXT6000T / 10000T - 240X ONLY Models whose part number ends with a “240X” are fitted with a single-phase isolating output transformer and are se
15NOTES FOR GXT6000T / 10000T - 240X ONLY 1. The installer must provide circuit breaker protection according to local codes. Maintain service space
16STABILIZERS / LEVELING FEET When the UPS is located in its final position before or after wiring, it is necessary to fit stabilizer brackets and,
17FERRITE BEAD INSTALLATION When using either of the options below, to reduce the risk of radio interference, fit the ferrite assemblies supplied wi
18 COMMISSIONING THE UPS Output Voltage Selector Switches The Output Voltage Selector Switches, located on the rear of the UPS, are designed to allo
19 CONTROLS AND INDICATORS Fault Indicator (Red) The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the loa
2 IMPORTANT SAFETY INSTRUCTIONS WARNING: Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently
20Load/Battery Level Indicators (4 Green, 1 Amber) The Load/Battery Level indicators have dual functions. During NORMAL mode operation LED indicato
21 InputBreakerOutputBreakerBatteryBreakerBatteryBreakerGXT 6 & 10 kVAComponent Diagram208 Models ShownHardwireTerminal BlocksHardwireTerminal B
22OPERATING MODES NORMAL MODE OPERATION- UPS mode During normal operation, utility power provides energy to the UPS. The filters, the power factor
23BYPASS MODE OPERATION During BYPASS operation, utility power provides energy to your load and maintains the batteries in a fully charged state. Th
24MANUAL OPERATION WITH UTILITY AVAILABLE Under normal circumstances, the UPS will be operated with utility available. The UPS can operate in three
25POWERING DOWN THE UPS WITH UTILITY AVAILABLE 1. Shutdown all connected load equipment. 2. Press the OUTPUT OFF/BYPASS button once until a "be
26POWERING UP THE UPS WITHOUT UTILITY 1. Ensure the load equipment is turned off, and all loads are properly connected to the UPS output. 2. Verify
27COMMUNICATIONS UPS MONITORING The UPStation GXT UPS has the capability of being monitored with stand alone computers, network workstations, networ
28COMMUNICATIONS INTERFACE PORT The UPStation GXT UPS contains a standard DB-9 socket located on the rear of the UPS unit. Several signals are prov
29 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT develops a problem. Use
38. Never block or insert any object into the ventilation holes or other openings. 9. DO NOT CONNECT equipment that could overload the UPS or demand
30 AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds Low battery Two short beeps every fiv
31TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION Fault indicators and all load level LED's are illuminated UPS overloaded or load equipment is
32 MAINTENANCE The UPStation GXT UPS requires very little maintenance. The batteries are valve regulated, nonspillable, lead acid, and should be k
33 SPECIFICATIONS MODEL NUMBER GXT6000T-208 GXT10000T-208 MODEL RATING VA/W (max) 5400 / 3780 9000 / 6300 DIMENSIONS: mm (in) Unit W x D x H 260
34SPECIFICATIONS MODEL NUMBER GXT6000T-208X GXT10000T-208X MODEL RATING VA/W (max) 5400 / 3780 9000 / 6300 DIMENSIONS: mm (in) Unit W x D x H 26
35SPECIFICATIONS MODEL NUMBER GXT6000T-240X GXT10000T-240X MODEL RATING VA/W (max) 6000 / 4200 10000 / 7000 DIMENSIONS: mm (in) Unit W x D x H 2
36 LIMITED WARRANTY Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as th
Technical Support Global Services 1-800-LIEBERT Applications U.S.A. 1-800-222-5877 Outside the U.S.A. 614-841-6755 U.K. +44
4INTRODUCTION Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomput
5 MAJOR COMPONENTS EMI /RFI FILTERS These UPS components provide surge protection, and filter both electromagnetic interference (EMI) and radio fre
6STATIC BYPASS The UPStation GXT provides an alternate path for utility power to the connected load, in the unlikely event of a UPS malfunction. Sho
7INSTALLATION These instructions are for use by competent personnel only. INSTALLATION CONSIDERATIONS Detailed instructions to help you install the
8 Model AIRFLOW DISSIPATION* OUTPUT RATING** # Cfm m3h Watts K Btu/hr VA Watts GXT6000T 130 221 504 1.7 6000 4200 GXT10000T 270 459
9Connecting the UPS Power cables Power cables connect to screw terminals on a terminal block that is located behind the rear mounted cable box (see f