POWER PROTECTIONUSER MANUALEnglish700-2200 VA120 VPowerSure™ InteractiveR
10POWERSURE™ INTERACTIVE RACKMOUNT2200 Model1 3462361555700-1400 Models*700 Model has detachable cord1- Output Receptacles2- DB-9 Interface Port3- AC
11OPERATIONNORMAL MODE OPERATIONDuring normal operation, utility power provides energy to the UPS. The filters andthe power conditioning circuit proc
12BATTERY MODE OPERATIONBattery mode occurs in event of extreme input conditions or complete utility failure.The battery system along with the bi-dire
13COMMUNICATIONS INTERFACE PORTThe PowerSure™ Interactive UPS contains a standard DB-9F recepticle located onthe rear of the UPS unit. Several signal
14UPS INTELLIGENT COMMUNICATIONSThe PowerSure™ Interactive UPS has the capability to communicate intelligentlywith stand alone computers, network work
15MINI-TOWER BATTERY REPLACEMENTCAUTION- A battery can present a risk of electrical shock and high short circuitcurrent. The following precautions sh
16MINI-TOWER BATTERY REPLACEMENT700 VA ModelTo Disconnect: Gently pull wiringawayTo Connect: Connect red wire tored terminal, then black wire toblac
17RACKMOUNT BATTERY REPLACEMENTCAUTION- A battery can present a risk of electrical shock and high short circuitcurrent. The following precautions sho
18Figure 3Figure 5Figure 4Figure 1Figure 2Figure 6Figure 7
19TROUBLESHOOTINGThe information below indicates various symptoms a user may encounter in theevent the PowerSure™ Interactive UPS develops a problem.
2IMPORTANT SAFETY INSTRUCTIONSWARNING: Do not attempt to service this product yourself except to replacethe battery. Opening or removing the cover m
20TROUBLESHOOTING GUIDEPROBLEM CAUSE SOLUTIONUPS output short circuited oroverloaded.Ensure UPS is off. Disconnect allloads and ensure nothing islodg
21POWERSURE™ INTERACTIVETYPICAL BATTERY DISCHARGE CURVES(Discharge times are at 25° C ambient)0 25 50 75 100020406080Percent LoadRun Time (Mins)0 25 5
22AUDIBLE ALARM CONDITIONSCONDITION ALARMBattery mode(utility failure)One short beep every ten seconds; more than twominutes of run time remainingLow
23 MINI-TOWER SPECIFICATIONSModel Number PS700MT-120 PS1000MT-120 PS1400MT-120 PS2200MT-120Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 16
24RACKMOUNT SPECIFICATIONSModel NumberPS700RM-120 PS1000RM-120 PS1400RM-120 PS2200RM-120Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600D
25
1050 Dearborn Drive Columbus, OH 43229 614-888-0246Technical SupportU.S.A...1-800-222-
3it, or the safety ground will be removed. Operate UPS only from aproperly grounded 120 VAC outlet (2 wire plus ground).9. The UPS is equipped with
4INTRODUCTION & SYSTEM DESCRIPTIONCongratulations on your choice of the Liebert PowerSure™ InteractiveUninterruptible Power System (UPS). It prov
5MAJOR COMPONENTSTRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERSThese UPS components provide surge protection and filter Electromagneti
6MINI-TOWER INSTALLATION1. Unpack the UPS carefully noting the packing method. Retain the box andpacking material for possible future shipment.CAUTI
7RACKMOUNT INSTALLATION1. Unpack the UPS carefully noting the packing method. Retain box and packingmaterial for possible future shipment.CAUTION:
8CONTROLS AND INDICATORSOn/Off ButtonThe On/Off button controls output power to connected load(s).CAUTION: Pressing the On/Off button when AC utility
9POWERSURE™ INTERACTIVE MINI-TOWER4262642113543516153 700 VA 1000 / 1400 VA 2200 VAFault IndicatorLoad/BatteryLevel IndicatorsAlarm Silen